2015 Cummins Power Generation Generator Set | 2016 Cummins Power Generation Generator Set | 2018 Cummins Power Generation Generator Set | 2017 Cummins Power Generation Generator Set — Electrical system: wiring

Published August 7, 2018 · Recall initiated: July 31, 2018

Summary

NHTSA records recall 18V504000, published August 7, 2018 and initiated July 31, 2018. Recalling firm: Cummins, Inc.; 2015 Cummins Power Generation Generator Set | 2016 Cummins Power Generation Generator Set | 2018 Cummins Power Generation Generator Set | 2017 Cummins Power Generation Generator Set — Electrical system: wiring.

What's the hazard

Cummins Inc. (Cummins) is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and shut down the generator as intended.

What to do

Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.

Get an email if CUMMINS POWER GENERATION has another recall

Free. We only write when there's a new recall that matches. Unsubscribe in one click.

Recall details

Brand
CUMMINS POWER GENERATION
Model
GENERATOR SET
Manufacturer
Cummins, Inc.
Lot
2015 CUMMINS POWER GENERATION GENERATOR SET | 2016 CUMMINS POWER GENERATION GENERATOR SET | 2018 CUMMINS POWER GENERATION GENERATOR SET | 2017 CUMMINS POWER GENERATION GENERATOR SET
Risk classification
V
Country
US

Related recalls

Questions about this recall

Was 2015 Cummins Power Generation Generator Set | 2016 Cummins Power Generation Generator Set | 2018 Cummins Power Generation Generator Set | 2017 Cummins Power Generation Generator Set — Electrical system: wiring recalled?

Yes. NHTSA published recall 18V504000 on August 7, 2018. Reported hazard: Cummins Inc. (Cummins) is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and shut down the generator as intended.

What should I do if I have this product?

Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.

How do I know if my unit is part of the recall?

Compare your product details with the notice. Brand: CUMMINS POWER GENERATION. Model: GENERATOR SET.