MA/MH circuit breakers
Published November 14, 2025 · Recall initiated: August 9, 2002
What's the hazard
The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.
What to do
Contact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.
Recall details
- Brand
- Square D Company, of Palatine, Ill.
- Manufacturer
- Square D Company, of Palatine, Ill.
- Distributor
- The circuit breakers were sold between October 2000 and March 2002 for between $3,000 and $9,000.