CPSCCPSC · Productos de consumo·N.º oficial 01503
Mini-Mate2 Environmental Control Units
Publicado el 8 de abril de 2026 · Inicio del retiro: 8 de noviembre de 2000
Qué peligro representa
An electric heating element inside the system, that is used primarily in the dehumidification process, can short circuit and produce sparks, posing a smoke and fire risk.
Qué hacer
For more information about the recall, contact Liebert Corp. for instructions on disconnecting the reheat assembly. Liebert Corp. will install and replace the heating element. Liebert Corp. sent recall notices to known purchasers.
Detalles del retiro
- Marca
- Liebert Corp., of Columbus, Ohio
- Fabricante
- Liebert Corp., of Columbus, Ohio
- Distribuidor
- Liebert Corp. sold these units nationwide, from January 1998 through August 2000, for between $3,000 and $8,000.
- País
- US