MA/MH circuit breakers
Publicado el 9 de agosto de 2002
Resumen
CPSC registra el retiro 02556, publicado el 9 de agosto de 2002. Empresa responsable: Square D Company, of Palatine, Ill.; Unidades reportadas: About 40,000.
Qué peligro representa
The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.
Qué hacer
Contact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.
Recibe un correo si Square D vuelve a tener un retiro
Gratis. Solo te escribimos cuando hay un retiro nuevo que coincide. Te das de baja con un clic.
Detalles del retiro
- Marca
- Square D Company, of Palatine, Ill.
- Fabricante
- Square D Company, of Palatine, Ill.
- Distribuidor
- The circuit breakers were sold between October 2000 and March 2002 for between $3,000 and $9,000.
- País
- US
Retiros relacionados
- CPSCBicycle stems installed on 2002 and 2003 Cannondale bicycles15 de agosto de 2002
- CPSCMarin-brand mountain bikes with aluminum frames15 de agosto de 2002
- CPSCBTU window air conditioners14 de agosto de 2002
- CPSCMotorola DCT2000 digital cable set-top boxes8 de agosto de 2002
- CPSCEngines used on fun-karts8 de agosto de 2002
- CPSCBullet Speed Skates7 de agosto de 2002
Preguntas sobre este retiro
¿MA/MH circuit breakers fue retirado del mercado?
Sí. CPSC publicó el retiro 02556 el 9 de agosto de 2002. Peligro reportado: The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.
¿Qué debo hacer si tengo este producto?
Contact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.
¿Cómo sé si mi unidad está incluida en el retiro?
Compara los datos de tu producto con los del aviso. Marca: Square D Company, of Palatine, Ill..