Volver al buscador
CPSCCPSC · Productos de consumo·N.º oficial 07507

K-GUARD®, SENTRY® and FLAG FIRE® Model Fire Extinguishers

Publicado el 23 de mayo de 2014 · Inicio del retiro: 13 de noviembre de 2006

Qué peligro representa

If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.

Qué hacer

Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.

Detalles del retiro

Marca
Ansul Incorporated, of Marinette, Wis.
Fabricante
Ansul Incorporated, of Marinette, Wis.
Distribuidor
Ansul Incorporated, through its authorized fire equipment distributors, from May 2003 through September 2005. Extinguishers were sold by distributors to their end users for about $150 to $225 each for the kitchen units and for about $100 each for the water units.
País
US
Ver aviso oficial de CPSC

¿Vendes productos como este?

Recalert vigila todo tu catálogo contra retiros como este, automáticamente.

Empezar gratis — sin tarjeta