Volver al buscador
CPSCCPSC · Productos de consumo·N.º oficial 12721

Fire Alarm Control Panel

Publicado el 14 de abril de 2016 · Inicio del retiro: 15 de febrero de 2012

Qué peligro representa

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Qué hacer

All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

Detalles del retiro

Marca
Bosch Security Systems, Inc., of Fairport, N.Y.
Fabricante
Bosch Security Systems, Inc., of Fairport, N.Y.
Distribuidor
Authorized distributors and installers nationwide from May 2009 through October 2011 for about $1,200.
País
US
Ver aviso oficial de CPSC

¿Vendes productos como este?

Recalert vigila todo tu catálogo contra retiros como este, automáticamente.