CPSCCPSC · Productos de consumo·N.º oficial 18731
Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option
Publicado el 19 de marzo de 2018 · Inicio del retiro: 19 de marzo de 2018
Qué peligro representa
The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.
Qué hacer
Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.
Detalles del retiro
- Marca
- Carrier México, S.A. de C.V.
- Fabricante
- Carrier México, S.A. de C.V.
- Distribuidor
- Carrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.
- País
- US